Quick Mode
Overview
Quick Mode is an option of the tag [Interval] setting that lets users see near real-time values on the Data Source page and in dashboards.
How It Works
Value Upload
- When a value changes, the HMI uploads it immediately. While users are viewing the tag, or when the tag is referenced by an alarm rule, values are uploaded as often as about once per second.
- When a tag has historical data storage enabled, the HMI uploads the value at least once every 60 seconds, even if it does not change.
Historical Data Storage
- For each tag, historical data is written only after about 60 seconds have passed since the previous write, using the first value received after that point.
- If a value changes and returns within 60 seconds, historical data does not record the change.
- The timestamp of historical data is the time of the value on the HMI.
Alarm Evaluation
- Alarm rules that reference a Quick Mode tag are evaluated at most about once every 60 seconds; this also applies to tags without historical data storage enabled.
- Each evaluation compares the value with the value at the previous evaluation; a state change between two evaluations (for example, from normal to over the limit) is detected at the next evaluation if it persists until then.
- A limit violation that appears and disappears between two evaluations is not detected and does not create an alarm record.
- The trigger and recovery times of an alarm are the time of the value on the HMI.
Timeline Example
The following example assumes a tag uses Quick Mode, has historical data storage enabled, and is monitored by an over-limit alarm rule.
| T0 | T0+10 s | T0+70 s | T0+70 s (if recovered) | |
|---|---|---|---|---|
| HMI upload | Value: normal | Value: over the limit (uploaded on change) | Value: still over the limit (60 s upload) | Value: back to normal |
| Historical data | Written, timer starts | Skipped (10 s since last) | Written (70 s since last) | Written (70 s since last) |
| Alarm evaluation | Evaluated: not triggered | Skipped (10 s since last) | Evaluated: triggered | Evaluated: not triggered |
| Alarm record | None | None; this violation is not evaluated | Triggered at T0+70 s | None |
Notes
- After you modify tag settings, or modify HMI settings such as its name or location, the next value is processed immediately regardless of the 60-second limit, and the timer starts over.
- When an older value arrives late because of network delay, or a historical data write fails, historical data and alarms may be inconsistent once; this is usually resolved at the next processing.
- For values whose short-lived changes must be recorded, we currently recommend using a fixed interval or handling these changes on the HMI instead of relying on Quick Mode historical data or alarms. The 60-second processing interval will become configurable in the future, allowing a shorter or longer value.
- For how to set up alarm rules, see the Alarm documentation.